Protection from ground faults in the stator winding of generators at power plants in the Siberian Networks / R. A. Weinstein (Vaynshteyn) [et al.]

Уровень набора: Power Technology and EngineeringАльтернативный автор-лицо: Weinstein (Vaynshteyn), R. A., Specialist in the field of electric power engineering, Doctor of Technical Sciences, Professor of Tomsk Polytechnic University (TPU), 1937-, Robert Aleksandrovich;Lapin, V. I.;Naumov, A. M.;Doronin, A. V.;Yudin, S. M.Язык: английский.Страна: Россия.Резюме или реферат: The experience of many years of experience in developing and utilization of ground fault protection in the stator winding of generators in the Siberian networks is generalized. The main method of protection is to apply a direct current or an alternating current with a frequency of 25 Hz to the primary circuits of the stator. A direct current is applied to turbo generators operating in a unit with a transformer without a resistive coupling to the external grid or to other generators. Applying a 25 Hz control current is appropriate for power generation systems with compensation of a capacitive short circuit current to ground. This method forms the basis for protection of generators operating on busbars, hydroelectric generators with a neutral grounded through an arc-suppression reactor, including in consolidated units with generators operating in parallel on a single low-voltage transformer winding..Примечания о наличии в документе библиографии/указателя: References: p. 82 (18 tit.).Аудитория: .Тематика: труды учёных ТПУ
Тэги из этой библиотеки: Нет тэгов из этой библиотеки для этого заглавия. Авторизуйтесь, чтобы добавить теги.
Оценка
    Средний рейтинг: 0.0 (0 голосов)
Нет реальных экземпляров для этой записи

References: p. 82 (18 tit.)

The experience of many years of experience in developing and utilization of ground fault protection in the stator winding of generators in the Siberian networks is generalized. The main method of protection is to apply a direct current or an alternating current with a frequency of 25 Hz to the primary circuits of the stator. A direct current is applied to turbo generators operating in a unit with a transformer without a resistive coupling to the external grid or to other generators. Applying a 25 Hz control current is appropriate for power generation systems with compensation of a capacitive short circuit current to ground. This method forms the basis for protection of generators operating on busbars, hydroelectric generators with a neutral grounded through an arc-suppression reactor, including in consolidated units with generators operating in parallel on a single low-voltage transformer winding.

Для данного заглавия нет комментариев.

оставить комментарий.